• Weatherproof metal enclosure
  • 2 ¾” X 4 ½ “X 2”, mtg. ¾” knockout Or L bracket mount
  • All mode protection L – N, L – G, N – G, L – L
  • Single and three phase
  • Multi-voltage use

The LPC 11765U-13E and -1E models provide light duty protection on any voltage system up to and including 480 VRMS, single and three phase. The two models substitute for at least 15 models of individual voltage ratings, eliminating the need for many separate SPD’s in inventory.

The SPD’s mount through a ¾” knockout or use an “L” shaped bracket. The enclosure is weatherproof and may be installed in fused panels, inside equipment cabinets, or on the equipment itself.      

Protection is provided in all modes, i.e. each line to neutral, each line to ground, neutral to ground, and line to line. Response is less than 5 nanoseconds and only overvoltage transients are clamped. These SPD’s do not pass follow current, and stop conduction instantaneously once the voltage returns to normal. These SPD’s are not intended for the service entrance but for use deeper within the facility where surges are expected to be less severe.

Each model consists of 5 wires, each 6” long, for connection across the system wiring: for the hot wires, 3 black wires; for the neutral, 1 white wire; for earth ground, 1 green wire. The metal enclosure has provision for the safety wire (supplied by the customer). The 5 wires protrude through a threaded ¾” nipple located in the center of the 2¾” X 4½” face.

These SPD’s are not repairable. A defective SPD fails short circuit, in which case the line/branch fuses or breakers operate. A prolonged short circuit may open, and in the process cause rupture of the SPD elements.


Click on Model for more details
Unit of Measure
Items
Multi-Voltage Secondary AC Power (SPD)

Multi-Voltage Secondary AC Power (SPD)
Type N/A 50/60 Hz, single/three phase, voltage to 240 VRMS, 20-45 KA surge current N/A 50/60 Hz, single/three phase, voltage to 480 VRMS, 15-30 KA surge current
For N/A 120/240V -- 3W+G, 1 phase 120V -- 2W+G, 1 phase 208Y/120V -- 4W+G, 3 phase wye 240/120V -- 4W+G, 3 phase high leg delta 240V -- 2W+G, 1 phase 240V -- 3W+G, 3 phase delta N/A 240/480V -- 3W+G, 1 phase 240V -- 2W+G, 1 phase 380V -- 3W+G, 3 phase delta 380Y/220V -- 4W+G, 3 phase wye 415Y/240V -- 4W+G, 3 phase wye 480V -- 2W+G, 1 phase 480V -- 3W+G, 3 phase delta 480Y/277V -- 4W+G, 3 phase wye
Response N/A Less than 5 nanoseconds
Protection N/A All modes
Applicable Standards N/A ANSI/IEEE Standards: All C62 that apply UL Listed Std: 1449
Category N/A A, B, and C for light duty
Maximum Surge Current N/A 20KA to 45KA, 8/20 µs per phase
Energy N/A 3800 joules total