The LPC 11765U-13E and -1E models provide light duty protection on any voltage system up to and including 480 VRMS, single and three phase. The two models substitute for at least 15 models of individual voltage ratings, eliminating the need for many separate SPD’s in inventory.
The SPD’s mount through a ¾” knockout or use an “L” shaped bracket. The enclosure is weatherproof and may be installed in fused panels, inside equipment cabinets, or on the equipment itself.
Protection is provided in all modes, i.e. each line to neutral, each line to ground, neutral to ground, and line to line. Response is less than 5 nanoseconds and only overvoltage transients are clamped. These SPD’s do not pass follow current, and stop conduction instantaneously once the voltage returns to normal. These SPD’s are not intended for the service entrance but for use deeper within the facility where surges are expected to be less severe.
Each model consists of 5 wires, each 6” long, for connection across the system wiring: for the hot wires, 3 black wires; for the neutral, 1 white wire; for earth ground, 1 green wire. The metal enclosure has provision for the safety wire (supplied by the customer). The 5 wires protrude through a threaded ¾” nipple located in the center of the 2¾” X 4½” face.
These SPD’s are not repairable. A defective SPD fails short circuit, in which case the line/branch fuses or breakers operate. A prolonged short circuit may open, and in the process cause rupture of the SPD elements.
Type |
N/A 50/60 Hz, single/three phase, voltage to 240 VRMS, 20-45 KA surge current |
For |
N/A 120/240V -- 3W+G, 1 phase 120V -- 2W+G, 1 phase 208Y/120V -- 4W+G, 3 phase wye 240/120V -- 4W+G, 3 phase high leg delta 240V -- 2W+G, 1 phase 240V -- 3W+G, 3 phase delta |
Response |
N/A Less than 5 nanoseconds |
Protection |
N/A All modes |
Applicable Standards |
N/A ANSI/IEEE Standards: All C62 that apply UL Listed Std: 1449 |
Category |
N/A A, B, and C for light duty |
Maximum Surge Current |
N/A 20KA to 45KA, 8/20 µs per phase |
Energy |
N/A 3800 joules total |
120V, 2W+G, 1 Phase |
N/A Connect any 2 black wires together to L (hot) power wire; connect remaining black wire and white wire together to N (neutral) power wire; connect green wire to ground. |
120/240V, 3W+G 1 Phase |
N/A Connect any 2 black wires together to one L (hot) power wire; connect remaining black wire to the other L (hot) power wire; connect white wire to N (neutral) power wire; connect green wire to ground. |
240V, 3W+G, 3 Phase Delta |
N/A Connect each of the 3 black wires to each of the 3 L (hot) power wires; connect white wire together with green wire to ground. |
208Y/120V, 4W+G, 3 Phase Wye |
N/A Connect each of the 3 black wires to each of the 3 L (hot) power wires; connect white wire to N (neutral) power wire; connect green wire to ground. |
240/120V, 4W+G, 3 phase, High Leg Delta |
N/A Connect each of the 3 black wires to each of the 3 L (hot) power wires. Because of the symmetry of the suppressor design, any black wire may be used as the high leg; connect white wire to N (neutral) power wire; connect green wire to ground. |