Print Back

Miniature wire pair protector (4-20 ma transmitter protector). 2 lines and ground. 0.50" X 0.68" X 1.25" H. AWG 16 insulated leads. Protection maximum 30 KA, 8/20 µs line to line and each line to ground. Connections across the lines and to ground at or inside the equipment enclosure. Response less than a nanosecond. After initial breakdown clamping voltage immediately drops to 30V an any surge up to 30 KA of current. Automatic restoration to the line voltage after the surge passes.

Inquire regarding other available voltage ratings.
LPC10643series2
Unit of Measure
1 

Models available (examples)

For

LPC 10643-2 N/A 18V peak (DC and AC)
LPC 10643-24 N/A 28V peak (DC and AC)
LPC 10643-1 N/A 50V peak (DC and AC)
LPC 10643-60 N/A 65V peak (DC and AC)
Unit of Measure