AC POWER CIRCUITS
AC Power Circuits 60 to 100 Hz, 120 to 700 VAC -- Single and Three Phase
60 to 100 Hz, 120 to 700 VAC
Single and Three Phase
Single and Three Phase
Unit of Measure
Items |
/Asset/a0001001.jpg LPC 90593-120-1 MOV type |
/Asset/a0001001.jpg LPC 90593-120-2 MOV type |
/Asset/a0001001.jpg LPC 90593-120/240 MOV type |
/Asset/a0001001.jpg LPC 90593-240 MOV type |
/Asset/a0001001.jpg LPC 90593-440 MOV type |
|||||
System Voltage | N/A 120 VAC | N/A 120 VAC | N/A 120/240VAC | N/A 240 VAC | N/A 440 VAC | |||||
Number of Wires and Phases | N/A 2 wire, single phase | N/A 2 wire floating, single phase | N/A 3 wire, single phase (line to line 240VAC) | N/A two 2 wire floating, single phase | N/A 2 wire floating, single phase | |||||
MCOV | N/A 150 VAC, 4000 joules per mode | N/A 150 VAC, 4000 joules per mode. | N/A 150 VAC, 2500 joules per mode. | N/A 300 VAC, 6000 joules per mode. | N/A 550 VAC, 7000 joules per mode. | |||||
Load | N/A Series or T connection for unlimited load current. | |||||||||
Mounting | N/A Mounting two holes 0.265” D on 5.75” center (for standard mounting means). | |||||||||
Protection | N/A line to neutral and line to ground protection. | N/A line to line and each line to ground protection. | N/A each line to neutral, each line to ground and neutral to ground protection. | N/A line to line and each line to ground protection. | N/A line to line and each line to ground protection. | |||||
Maximum Surge Current | N/A 100 KA per mode | |||||||||
|